The gasoline vapour recovery system VARECO VENT/ TSMF (Stage I and II) is a 2 stages compact system with active carbon and membrane technology.
	The system consists of three parts, namely the processing unit, the cooling and the control cabinet. The system is built as a module in a steel cabinet and can be extended with additional individual modules. It is prefabricated, preassembled and tested and can be easily placed on a foundation.
	VARECO VENT/ TSMF allows a recovery rate of up to 99% of the vaporized fuel and thus meets the requirements of 20 and 21 BImSchV (German Federal Pollution Control Act).
	The system can be used both at gas stations and on tanker terminals.
	Process Description
	VARECO VENT /TSMF works with the adsorption forces of the membranes. Adsorption means the process of accretion or concentration of a liquid or a gas on a solid surface. Because of the overpressure in the storage tank, the fuel vapour enriched air flows into the condensate trap. The vapour condense there mostly to liquid fuel. The remaining vapours flow together with the air through the membranes. The membranes absorb the fuel vapours like a sponge, so that only clean air comes out of the system. During the air purification process and under the influence of the negative pressure on the other side of the membranes the fuel vapours desorb. The required negative pressure is generated by the vacuum pump.
	The recovered product is collected in the condensate trap and carried back into the storage tank. For better emission values the air, passes out of the membrane module, is purified additionally by an activated carbon filter.
	Capacity
	The maximum capacity of the plant is 50 m³/h.
	Emission Limit
	The emission limit of the system is less than 35g hydrocarbon per m³.
	Process Unit
	The process unit includes the whole process equipment like vacuum pumps, condensate trap, membrane module, magnetic valve, etc., and is designed to be installed inside hazardous areas (Ex-zones).
	Technical Data
	Feed vacuum pump
	Power supply: AC 380V / 400V
	Power: 2.2kW
	Performance: 1000 l/min
	Temperature of medium: up to 50°C
	Certification: ATEX EX II 1/2 G IIB3 T3/T4
	Permeate vacuum pump
	Power supply: AC 380V / 400V
	Power: 0.37kW
	Performance: 260 l/min
	Temperature of medium: up to 50°C
	Certification: ATEX EX II 1/2 G IIB3 T3/T4
	Refrigerant unit
	Power supply: AC 380V / 400V 50Hz
	Power: 2.6kW or 4.24kW
	Cooling capacity: 5.1kW or 9.29kW
	Ambient temperature: -10°C up to +50°C
	Refrigerant: R410A
	Medium: Water-Glycol
	Plant
	Dimensions (w x h x d): 1450 x 1830 x 1750mm
	Weight: 600kg
	Power supply: AC 400V - 5kW or 7kW
	Connection cable: 5G6
	Performance: 50m3/h
	Pipe connections
	Connection vapour: G 2"
	Connection condensate: G 1"
	Membranes: 8 - 12 m²
	Certifications: DEKRA / ATEX